krx wrote: > > "vytjon" <no@any.mail> wrote in message > news:hb3oek$82b$1@trimpas.omnitel.net... >> krx wrote: >>> Grubiai tariant VA ir W priklauso nuo tavo naudojamos apkrovos tipų, >>> šiuo atveju - maitinimo bloko efektyvumo, PFC naudojimo maitinimo bloke. >> >> Pamiršau paminėti - jeigu maitblokiai su aktyviu PFC pvz. Delta >> gamybos - su mažo galingumo UPS'u turėsi problemų :) > > Kokių? Kai kurios PSU+UPS kombinacijos dingus įtampai pakabina UPS'ą. Dažniausiai keiksnojami Delta gaminti maitinimo šaltiniai (LT paprastai pasitaiko su Chieftec etikete). "Power supplies manufactured by Delta Electronics are notorious for offering poor compatibility with UPSes. The problem is in their active PFC device. It is designed in such a way that at the moment of switching to the batteries it creates high short-term load on the UPS, triggering the latter’s protection. You can only solve this problem by replacing the UPS with a more advanced one (over 1000VA)."